9 Operation
65
Due to pressure drops in the system, the measured volume flow may
be smaller than the actual volume flow. The measured volume flow can
be corrected via the flow rate correction factor. The flow rate correction
factor has a directly proportional effect on the measurement result and
is usually set at 1.00. Once the factor is changed, the result is multiplied
by the flow rate correction factor.
Settings have been saved.
HVAC grid measurement
Activate HVAC grid measurement
using the slider.
Detailed information about a standard-compliant measurement can be
stored in order to have the measurement assistant determine the
optimum immersion depth of the probe in the duct.
Determine the Number of inspection holes (drilled holes).
Determine the Number of measuring points.
Determine the Inspection hole position.
A graphic with the number of inspection holes and measuring points is
displayed.