A.5 MODBUS (1X) INPUT REGISTERS FOR SINGLE PHASE UPS: ALARMS AND STATUS
All 1X registers are:
Data Type Discrete
Size 1-Bit
Access Read Only
Units True (1)/False (0)
Note 1: The Modbus registers table style addressing is protocol base 0. If monitoring software uses PLC style addressing base 1, add one to the register number. For
example, Modbus address 30001 becomes PLC address 30002 ; address 10001 becomes PLC address 10002.
Note 2: Please make sure the latest RemotEye 4 firmware revision is installed in order to use the Modbus register table below. If not, there will be inconsistencies
between RemotEye 4 internal register addressing and this manual. Go to www.toshibaups.com to get the latest RemotEye 4 firmware.
MODBUS (1X) INPUT REGISTER SINGLE PHASE PLATFORMS
Registers
Description
1600XP(i)
T1000
T1000 (1-3kVA)
CMD
CMD
CMD
RMTI
-4 Status
10001
RemotEye 4 Data Link
Y
Y
Y
10002
RemotEye 4 Network Link
Y
Y
Y
Reserved
N/A
N/A
N/A
….
Reserved
N/A
N/A
N/A
…..
Reserved
N/A
N/A
N/A
10020
Reserved
N/A
N/A
N/A
UPS Mode
10021
Startup Mode
Y
Y
N/A
10022
Online Mode
Y
Y
Y
10023
Backup Mode
Y
Y
Y
10024
Bypass Mode
Y
Y
Y
10025
Shutdown Mode
Y
Y
Y
10026
Battery Test Mode
Y
Y
Y
10027
Pre-Charge Mode
N/A
N/A
N/A
10028
Gate-Check Mode
N/A
N/A
N/A
10029
Standby Mode
N/A
N/A
N/A
10030
Power Conditioner
N/A
N/A
N/A
10031
Start Inverter
N/A
N/A
N/A
10032
Stop Inverter
N/A
N/A
N/A