RemotEye 4 User Manual – 90988-007 175
4300 BACnet Binary Input Point Mapping
Object Name & Description
1 = One or more fault reported, see below for cause; 0 = No
Faults
DC Bus Under Voltage During Boost-up Fault
DC Bus Under Voltage During Charging Fault
Charger Overvoltage Fault
Output Under Voltage Fault
Input Phase Rotation Error
Bypass Phase Rotation Error
Input Overvoltage Warning
Input Under voltage Warning
Input MCCB Tripped Warning
Bypass Overvoltage Warning
Bypass Under voltage Warning
Bypass Input Frequency Error Warning
Inverter Overload Warning
User Defined Overload Warning
upsAlarmUserDefinedOverloadWarning
Output Frequency is set at 50Hz
upsAlarmOutputFrequency50Hz
upsAlarmBatteryTestInProgress
Battery Test Failed Warning
upsAlarmBatteryVoltageNotGood
Low Battery Level Reached Warning
Shutdown Battery Level Reached Warning
Battery Near Expiration Warning (Replace batteries soon)
upsAlarmBatteryNearExpiration