7 Replacing the Measuring System
The following points must be noted when replacing the measuring system:
The new measuring system must have the same article number as the measuring
system being replaced; any deviations must be expressly clarified with
TR-Electronic.
It must be ensured that the counting direction set via hardware switches for the
new measuring system matches the previous counting direction.
The new measuring system must be installed in accordance with the
specifications and requirements in chapter "Assembly" on page 78.
The new measuring system must be connected in accordance with the
specifications in chapter "Connection/Shield cover" on page 87/90.
When recommissioning the replaced measuring system, correct functioning must
be ensured first of all by means of a protected test run.