6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
100.000
N/A*
[-999999.999 - 999999.999
N/A]
Enter the analog input scaling value that corresponds to the high voltage/
high current value set in par.6-21
Terminal 54 High Voltage and par.
6-23
Terminal 54 High Current.
6-26 Terminal 54 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s] Enter the time constant. This is a first-order digital low pass filter time
constant for suppressing electrical noise in terminal 54. A high time con-
stant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.
6-27 Terminal 54 Live Zero
Option: Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a de-central I/O
system (e.g. when not as part of any frequency converter related control
functions, but feeding a Building Management System with data).
[0] Disabled
[1] * Enabled
6-3* Analog Input 3 MCB 101
Parameter group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB
101.
6-30 Terminal X30/11 Low Voltage
Range: Function:
0.07 V* [0.00 - par. 6-31 V] Sets the analog input scaling value to correspond to the low reference/
feedback value (set in par.6-34
Term. X30/11 Low Ref./Feedb. Value).
6-31 Terminal X30/11 High Voltage
Range: Function:
10.00 V* [par. 6-30 - 10.00 V] Sets the analog input scaling value to correspond to the high reference/
feedback value (set in par.6-35
Term. X30/11 High Ref./Feedb. Value).
6-34 Term. X30/11 Low Ref./Feedb. Value
Range: Function:
0.000 N/
A*
[-999999.999 - 999999.999
N/A]
Sets the analog input scaling value to correspond to the low voltage val-
ue (set in par.6-30
Terminal X30/11 Low Voltage).
6-35 Term. X30/11 High Ref./Feedb. Value
Range: Function:
100.000
N/A*
[-999999.999 - 999999.999
N/A]
Sets the analog input scaling value to correspond to the high voltage
value (set in par.6-31
Terminal X30/11 High Voltage).
Parameter Description
118 TR200 Programming Guide