6-36 Term. X30/11 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing electrical
noise on terminal X30/11.
par.6-36
Term. X30/11 Filter Time Constant cannot be changed while the
motor is running.
6-37 Term. X30/11 Live Zero
Option: Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a decentral I/O
system (e.g. when not part of any frequency converter related control
functions, but feeding a Building Management System with data).
[0] * Disabled
[1] * Enabled
6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for analog input 4 (X30/12) placed on option module MCB
101.
6-40 Terminal X30/12 Low Voltage
Range: Function:
0.07 V* [0.00 - par. 6-41 V] Sets the analog input scaling value to correspond to the low reference/
feedback value set in par.6-44
Term. X30/12 Low Ref./Feedb. Value.
6-41 Terminal X30/12 High Voltage
Range: Function:
10.00 V* [par. 6-40 - 10.00 V] Sets the analog input scaling value to correspond to the high reference/
feedback value set in par.6-45
Term. X30/12 High Ref./Feedb. Value.
6-44 Term. X30/12 Low Ref./Feedb. Value
Range: Function:
0.000 N/
A*
[-999999.999 - 999999.999
N/A]
Sets the analog output scaling value to correspond to the low voltage
value set in par.6-40
Terminal X30/12 Low Voltage.
6-45 Term. X30/12 High Ref./Feedb. Value
Range: Function:
100.000
N/A*
[-999999.999 - 999999.999
N/A]
Sets the analog input scaling value to correspond to the high voltage
value set in par.6-41
Terminal X30/12 High Voltage.
6-46 Term. X30/12 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing electrical
noise on terminal X30/12.
par.6-46
Term. X30/12 Filter Time Constant cannot be changed while the
motor is running.
Parameter Description
TR200 Programming Guide 119