6-47 Term. X30/12 Live Zero
Option: Function:
This parameter makes it possible to disable the Live Zero monitoring.
E.g. to be used if the analog outputs are used as part of a decentral I/O
system (e.g. when not part of any frequency converter related control
functions, but feeding a Building Management System with data)
[0] * Disabled
[1] * Enabled
6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e. Terminal 42. Analog outputs are current
outputs: 0/4 – 20 mA. Common terminal (terminal 39) is the same terminal and has the same electrical potential
for analog common and digital common connection. Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option: Function:
Select the function of Terminal 42 as an analog current output. A motor
current of 20 mA corresponds to I
max
.
[0] * No operation
[100] Output freq. 0-100 : 0 - 100 Hz, (0-20 mA)
[101] Reference Min-Max : Minimum reference - Maximum reference, (0-20 mA)
[102] Feedback +-200% : -200% to +200% of par.20-14
Maximum Reference/Feedb., (0-20 mA)
[103] Motor cur. 0-Imax : 0 - Inverter Max. Current (par.16-37
Inv. Max. Current), (0-20 mA)
[104] Torque 0-Tlim : 0 - Torque limit (par.4-16
Torque Limit Motor Mode), (0-20 mA)
[105] Torque 0-Tnom : 0 - Motor rated torque, (0-20 mA)
[106] Power 0-Pnom : 0 - Motor rated power, (0-20 mA)
[107] * Speed 0-HighLim : 0 - Speed High Limit (par.4-13
Motor Speed High Limit [RPM] and par.
4-14
Motor Speed High Limit [Hz]), (0-20 mA)
[113] Ext. Closed Loop 1 : 0 - 100%, (0-20 mA)
[114] Ext. Closed Loop 2 : 0 - 100%, (0-20 mA)
[115] Ext. Closed Loop 3 : 0 - 100%, (0-20 mA)
[130] Out frq 0-100 4-20mA : 0 - 100 Hz
[131] Reference 4-20mA : Minimum Reference - Maximum Reference
[132] Feedback 4-20mA : -200% to +200% of par.20-14
Maximum Reference/Feedb.
[133] Motor cur. 4-20mA : 0 - Inverter Max. Current (par.16-37
Inv. Max. Current)
[134] Torq.0-lim 4-20 mA : 0 - Torque limit (par.4-16
Torque Limit Motor Mode)
[135] Torq.0-nom 4-20mA : 0 - Motor rated torque
[136] Power 4-20mA : 0 - Motor rated power
[137] Speed 4-20mA : 0 - Speed High Limit (4-13 and 4-14)
[139] Bus ctrl. : 0 - 100%, (0-20 mA)
[140] Bus ctrl. 4-20 mA : 0 - 100%
Parameter Description
120 TR200 Programming Guide