0-02 Motor Speed Unit
Option: Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par.0-02
Motor Speed Unit
and par.0-03
Regional Settings. The default setting of par.0-02 Motor
Speed Unit and par.0-03 Regional Settings depends on which region of
the world the frequency converter is supplied to, but can be re-program-
med as required.
Note
Changing the
Motor Speed Unit
will reset certain parameters to their initial
value. It is recommended to select the motor speed unit first, before
modifying other parameters.
[0] RPM Selects display of motor speed variables and parameters (i.e. references,
feedbacks and limits) in terms of motor speed (RPM).
[1] * Hz Selects display of motor speed variables and parameters (i.e. references,
feedbacks and limits) in terms of output frequency to the motor (Hz).
0-03 Regional Settings
Option: Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in par.0-02
Motor Speed Unit
and par.0-03
Regional Settings. The default setting of par.0-02 Motor
Speed Unit and par.0-03 Regional Settings depends on which region of
the world the frequency converter is supplied to but can be re-program-
med as required.
[0] * International Sets par.1-20
Motor Power [kW] units to [kW] and the default value of
par.1-23
Motor Frequency [50 Hz].
[1] * North America Sets par.1-21
Motor Power [HP] units to HP and the default value of par.
1-23
Motor Frequency to 60 Hz.
The setting not used is made invisible.
0-04 Operating State at Power-up
Option: Function:
Select the operating mode upon reconnection of the frequency converter
to mains voltage after power down when operating in Hand (local)mode.
[0] * Resume Resumes operation of the frequency converter maintaining the same
local reference and the same start/stop condition (applied by [Hand On]/
[Off] on the keypad or Hand Start via a digital input as before the fre-
quency converter was powered down.
[1] Forced stop, ref=old Uses saved reference [1] to stop the frequency converter but at the same
time retain in memory the local speed reference prior to power down.
After mains voltage is reconnected and after receiving a start command
(using the keypad [Hand On] button or Hand Start command via a digital
input) the frequency converter restarts and operates at the retained
speed reference.
Parameter Description
40 TR200 Programming Guide

Table of Contents

Other manuals for Trane TR200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TR200 Series and is the answer not in the manual?

Trane TR200 Series Specifications

General IconGeneral
Input Voltage24 VAC
Frequency Range50/60 Hz
Communication ProtocolsBACnet MS/TP, Modbus RTU
Controller TypeProgrammable
Power Range20 VA
Control MethodPID Control
Enclosure RatingIP20
Operating Temperature32°F to 122°F (0°C to 50°C)
Humidity Range5% to 95% non-condensing
MemoryNon-volatile