0-05 Local Mode Unit
Option: Function:
Defines if the local reference unit should be displayed in terms of the
motor shaft speed (in RPM/Hz) or as percent.
[0] * As Motor Speed Unit
[1] %
0-1* Set-up Operations
Define and control the individual parameter set-ups.
The frequency converter has four parameter setups that can be programmed independently of each other. This
makes the frequency converter very flexible and able to meet the requirements of many different TR200 system
control schemes often saving the cost of external control equipment. For example these can be used to program
the frequency converter to operate according to one control scheme in one setup (e.g. daytime operation) and
another control scheme in another setup (e.g. night set back). Alternatively they can be used by an AHU or
packaged unit OEM to identically program all their factory fitted frequency converters for different equipment
models within a range to have the same parameters and then during production/commissioning simply select
a specific setup depending on which model within that range the frequency converter is installed on.
The active setup (i.e. the setup in which the frequency converter is currently operating) can be selected in par.
0-10
Active Set-up and is displayed in the keypad. Using Multi set-up it is possible to switch between set-ups
with the frequency converter running or stopped, via digital input or serial communication commands (e.g. for
night set back). If it is necessary to change setups whilst running, ensure par.0-12
This Set-up Linked to is pro-
grammed as required. For the majority of TR200 applications it will not be necessary to program par.0-12
This
Set-up Linked to even if change of set up whilst running is required, but for very complex applications, using
the full flexibility of the multiple setups, it may be required. Using par.0-11
Programming Set-up it is possible
to edit parameters within any of the setups whilst continuing the frequency converter operation in its Active
Setup which can be a different setup to that being edited. Using par.0-51
Set-up Copy it is possible to copy
parameter settings between the set-ups to enable quicker commissioning if similar parameter settings are re-
quired in different set-ups.
0-10 Active Set-up
Option: Function:
Select the set-up in which the frequency converter is to operate.
Use par.0-51
Set-up Copy to copy a set-up to one or all other set-ups. To
avoid conflicting settings of the same parameter within two different set-
ups, link the set-ups together using par.0-12
This Set-up Linked to. Stop
the frequency converter before switching between set-ups where pa-
rameters marked ‘not changeable during operation’ have different val-
ues.
Parameters which are ‘not changeable during operation’ are marked
FALSE in the parameter lists in the section
Parameter Lists
[0] Factory setup Cannot be changed. It contains the Trane data set, and can be used as a
data source when returning the other set-ups to a known state.
[1] * Set-up 1
Set-up 1
[1] to
Set-up 4
[4] are the four separate parameter set-ups within
which all parameters can be programmed.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up Is used for remote selection of set-ups using digital inputs and the serial
communication port. This set-up uses the settings from par.0-12
This
Set-up Linked to.
Parameter Description