CTV-SVU01B-EN • Tracer AdaptiView Display Operations Guide 25
Reports
Auto Waiting for Evaporator Water Flow
Waiting For A Need To Cool
Waiting For a Need To Heat
Power Up Delay Inhibit MIN:SEC
Waiting To Start Waiting For Condenser Water Flow
Establishing Oil Pressure
Pre-Lubrication Time MIN:SEC
Motor Temperature Inhibit: Motor Temperature/Inhibit Temperature
Restart Time Inhibit MIN:SEC
High Vacuum Inhibit: Oil Sump Press/Inhibit Press
Low Oil Temperature Inhibit: Oil Tem pe ratu re /In hi bi t Te mpe rat ure
Waiting for Starter To Start MIN:SEC
Starting Compressor No submode is displayed.
Running No submode is displayed
Hot Water Control
Surge
Base Loaded
Hot Gas Bypass
Ice Building
Ice To Normal Transition
Current Control Soft Loading
Capacity Control Soft Loading
Running—Limit Current Limit
Phase Unbalance Limit
Condenser Pressure Limit
Evaporator Temperature Limit
Minimum Capacity Limit
Maximum Capacity Limit
Free Cooling Opening Free Cooling Valves
Closing Free Cooling Limit
Preparing to Shutdown Closing IGV IGV Position %
Shutting Down Post-Lubrication Time MIN:SEC
Evaporator Pump Off Delay MIN:SEC
Condenser Pump Off Delay MIN:SEC
Table 6. Chiller submodes (continued)
Top-level mode Corresponding sub-level mode