Page #14 background image
1-4
Table 1-1.
A
utoPulse Z-10 Original 9
A
pplications With Original Relay Operation
Releasing Application
IDC 1 IDC 2 IDC 3 IDC 4 SPM1 SPM2 NAC1 NAC2 RAC1 RAC2 Timers Panel Aux Relays Relay Exp Board 1 (Hazard 1) Relay Exp Board 2 (Hazard 2)
Notes 1, 2, & 3 Note 4
Notes 4
& 5
Abort Rel. Aux1 Aux2 Aux3 Relay 1 Relay 2 Relay 3 Relay 4 Relay 1 Relay 2 Relay 3 Relay 4
1. Agent Release, Single Hazard, Cross-Zoned, Combined Release
Stage 1 - 1st Alarm
IDC 1 or 2 Alarm
Abort
MS
Steady Optional Opt
TBL Alarm
Supv or
Start
Release
Timer
(select.)
Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge
Stage 2 - Alarm Confirmed
IDC 1 & 2 Alarm Steady 120bpm Opt Start
Stage 3 - Release
Alarm
Steady Steady ON ON
Expired
Pressure Switch Alarm
Pressure Steady Steady
Tamper Switch (Supervisory)
Supv. Optional
2. Agent Release, Single Hazard, Combined Release
Stage 1 - Alarm IDC 1 or 2 Alarm
Abort
MS
Steady 120bpm
Opt Start
TBL Alarm
Supv Or
Pressure
(select.)
Trouble Alarm
Pressure
Switch
Alarm
Discharge Trouble Alarm
Pressure
Switch
Alarm
Discharge
Stage 2 - Release Alarm
Steady Steady ON ON
Expired
Pressure Switch Alarm Pressure Steady Steady
Tamper Switch (Supervisory) Supv. Optional
3. Agent Release, Dual Hazard, Cross-Zoned
Hazard 1, Stage 1 - 1st Alarm IDC 1 or 2 Alarm
Abort
MS
Optional Opt
TBL
Hazard
1 Auto
or
Manual
Alarm
Hazard 2
Auto or
Manual
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
2nd
Cross-
Zone
Alarm
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
2nd
Cross-
Zone
Alarm
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Alarm Confirmed IDC 1 & 2 Alarm 120bpm Opt Start
Hazard 1, Stage 3 - Release Alarm
Steady ON Expired
Hazard 2, Stage 1 - 1st Alarm IDC 3 or 4 Alarm
Abort
MS
Optional Opt
Hazard 2, Stage 2 - Alarm Confirmed IDC 3 & 4 Alarm 120bpm Opt Start
Hazard 2, Stage 3 - Release Alarm
Steady ON Expired
4. Agent Release, Dual Haza
r
d
Hazard 1, Stage 1 - Alarm IDC 1 or 2 Alarm
Abort
MS
120bpm Opt Start
TBL
Hazard
1 Auto
or
Manual
Alarm
Hazard 2
Auto or
Manual
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Start
Release
Timer
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Start
Release
Timer
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Release Alarm
Steady ON Expired
Hazard 2, Stage 1 - Alarm IDC 3 or 4 Alarm
Abort
MS
120bpm Opt Start
Hazard 2, Stage 2 - Release Alarm
Steady ON Expired
Releasing Application
IDC 1 IDC 2 IDC 3 IDC 4
SPM1 SPM2 NAC1 NAC2 RAC1 RAC2 Time-Limit Cutout
Panel Aux Relays Relay Exp Board 1 (Hazard 1) Relay Exp Board 2 (Hazard 2)
Note 6
Aux1 Aux2 Aux3
Relay 1 Relay 2 Relay 3 Relay 4 Relay 1 Relay 2 Relay 3 Relay 4
5. Preaction/Deluge, Single Hazard, Cross-Zoned
Stage 1 - 1st Alarm 1st IDC in Alarm Steady Optional Opt
TBL Alarm
Supv. or
Waterflow
(select.)
Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge
Stage 2 - Alarm Confirmed / Release 2nd IDC in Alarm Steady Steady ON ON Opt
Waterflow Alarm WF Steady Steady Note 7 Note 7
Supervisory Alert Supv Optional
6. Preaction/Deluge, Single Hazard, Combined Release
Releasing Alarm Any 1 or more IDC's in Alarm Steady ON ON Opt
TBL Alarm
Supv. or
Waterflow
(select.)
Trouble Alarm Waterflow Discharge Trouble Alarm Waterflow Discharge
Waterflow Alarm WF Steady Note 7 Note 7
Supervisory Alert Supv Optional
7. Preaction/Deluge, Dual Hazard, Cross-Zoned
Hazard 1, Stage 1 - Alarm IDC 1 or 2 Alarm Optional Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
2nd
Cross-
Zone
Alarm
Hazard 1
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
2nd
Cross-
Zone
Alarm
Hazard 2
Discharge
Hazard 2
Hazard 1, Stage 2 - Release IDC 1 & 2 Alarm Steady ON Opt
Hazard 2, Stage 1 - Alarm IDC 3 or 4 Alarm Optional Opt
Hazard 2, Stage 2 - Release IDC 3 & 4 Alarm Steady ON Opt
Waterflow Alarm (both hazards) WF Steady Steady Note 7 Note 7
Supervisory Alert (both hazards, no NAC) Supv
8. Preaction/Deluge, Dual Hazard
Hazard 1 - Releasing Alarm IDC 1 or 2 Alarm Steady ON Opt
TBL
Hazard
1
Alarm
Hazard 2
Alarm
System
or
Hazard
1 TBL
Hazard
1 Alarm
Waterflow
Hazard 1
or Hazard
2
Discharge
Hazard 1
System
or
Hazard
2 TBL
Hazard
2 Alarm
Waterflow
Hazard 1
or Hazard
2
Discharge
Hazard 2
Hazard 2 - Releasing Alarm IDC 3 or 4 Alarm Steady ON Opt
Waterflow Alarm (both hazards) WF Steady Steady Note 7 Note 7
Supervisory Alert (both hazards, no NAC) Supv
Releasing Application IDC 1 IDC 2 IDC 3 IDC 4 SPM1 SPM2 NAC1 NAC2 RAC1
NAC3
Timers Panel Aux Relays
Relay Exp Board 1 (Hazard 1) Relay Exp Board 2 (Hazard 2)
Note 8
Abort Rel. Aux1 Aux2 Aux3
Relay 1 Relay 2 Relay 3 Relay 4 Relay 1 Relay 2 Relay 3 Relay 4
9. Agent Release, Single Hazard, Cross-Zoned, NYC abort
Stage 1 - 1st Alarm IDC 1 or 2 Alarm
Abort
MS
Steady Opt
TBL Alarm
Supv. or
Start
Release
Timer
(select.)
Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge Trouble Alarm
2nd
Cross-
Zone
Alarm
Discharge
Stage 2 - Alarm Confirmed IDC 1 & 2 Alarm OFF 120bpm Steady Opt Start
Abort switch pressed Alarm Steady OFF OFF Opt Suspend
Abort switch released Alarm Steady OFF OFF Start
Investigate (Abort) Timer expired Alarm OFF 120bpm Steady Expired Reload
Stage 3 - Release Alarm
OFF Steady ON Steady
Expired
Pressure Switch Alarm Pressure Steady Steady
Tamper Switch (Supervisory) Supv. Optional
Style C Option
Releasing Application
IDC1 IDC2 IDC3 IDC4 SPM1 SPM2 NAC1 NAC2 RAC1 RAC2 Timers Panel AUX Relays
Style C Option Agent Release
Style C Operation: Current limited equals an
alarm; short/open equals a trouble
Same as Agent Release applications above
except all IDCs operate Style C.
Abort
(Style C)
MS
(Style C)
Same as Agent Release applications above except SPM1 and SPM2 are associated with both hazards.
Style C Option Preaction Deluge
Style C Operation: Current limited equals an
alarm; short/open equals a trouble
Same as Preaction/Deluge applications above except all IDCs and SPMs
operate Style C.
Same as Preaction/Deluge applications above except SPM1 and SPM2 are associated with both hazards.
NOTES:
1. SPM1 and SPM2 are combination Manual Release / Abort zones in Agent Release Dual Hazard applications only. A s
a Manual Release and a current limit is an Abort condition.
5. Where Temporal Code pattern is only allowed for evacuation signaling and the Audible NAC op
e
Cross-Zoned Alarm is changed from the default Temporal Code to 20bpm, NAC 2 should not be
Supervisory signaling.
2. A Manual Release will start the Releasing Timer and operate the NAC cadence pattern associated with the start of the
Release Timer in the I/O matrix for the application selected.
6. In Preaction/Deluge applications configured for Class A/B (i.e. non-Style C), a short on any IDC
immediate manual release.
3. A Manual Release will override an Abort. In an abort condition the NACs will operate in accordance with the active Sta
2, and 3 operation in the I/O matrix for application selected and the specific Abort operation selected.
7. In Preaction/Deluge applications configured for Style C operation, SPM2 activates a manual rel
e
hazards.
4. Optional operation is selectable for 20bpm or Temporal Code. When Temporal Code is selected for the Alarm NAC
operation, the Supervisory NAC signal will be 20BPM. When 20BPM is selected for the Alarm NAC operation, the
Supervisory NAC signal will be temporal code.
8. For application mode 9 only, RAC2 is not used as a releasing circuit; instead it becomes a third
N