3-18
For recommended procedures and guidelines on testing the IDCs, NACs and RACs, refer to
NFPA 72 (2002 Edition), Annex C "Wiring Diagrams and Guides for Testing Fire Alarm Circuits.
The detection level for the AutoPulse Z-10 is 10k ohms, minimum, on all circuits.
Testing Circuit Supervision
General
Earth Fault
Detection