F3200 Operator's Manual Document No: LT0119
Network Systems
Page 11-22 29 July 2002 Issue 2.04
OPERATING SEQUENCE - NETWORK ZONE RANGE (CONTINUED)
The LCD will display the network zone range with a message saying "Sending
Command". After a brief period, the message should change to "Network Command
Accepted". Refer to Section 11.7 for more details on these and other possible LCD
display messages.
Note that if the remote panel is unable to de-isolate all of the zones due to some having
an alarm or fault status, then a exception message will be received indicating this. Refer
to Section 11.7 for Exception Messages.
11.10.4.3 Notes
(i) The effect of the isolate/de-isolate command is dependent upon the remote
FIP type, eg. which zones will be isolated/de-isolated, how a zone is affected
by isolation/de-isolation, and so forth.
(ii) Refer to Section 7.2.4 for information on how an F3200 panel processes a
zone isolate/de-isolate command.
11.10.5 NETWORK ZONE RESET
11.10.5.1 Function
A Network Zone Reset command sends a Reset Zone(s) command to the remote FIP
that has the zone(s). If the network zone(s) are on the local FIP, the command is
implemented as a local zone(s) reset.
11.10.5.2 Operating Sequence - Single Network Zone
From the base display, press:
to reset network zone number n n n n n. Press ACK to initiate the reset command.