Document No: LT0119 F3200 Operator's Manual
Network Systems
Issue 2.04 29 July 2002 Page 11-23
Operating Sequence - Single Network Zone (Continued)
The LCD will display the network zone with a message saying "Sending Command".
After a brief period the message should change to "Command Accepted". Refer to
Section 11.7 for more details on these and other possible LCD display messages.
If an exception occurs at the remote FIP, then an exception display may be received
indicating the type of exception. Refer to Section 11.7 for Exception Messages.
11.10.5.3 Operating Sequence - Network Zone Range
From the base display, press:
to reset network zone numbers n n n n n to m m m m m. Press ACK to initiate the reset
command.
The LCD will display the network zones with a message saying "Sending Command".
After a brief period the message should change to "Command Accepted". Refer to
Section 11.7 for more details on these and other possible LCD display messages.
If an exception occurs at the remote FIP, then an exception display may be received
indicating the type of exception.
IMPORTANT
The range of zones entered must be limited to zones on a single
networked FIP, i.e. the range cannot encompass zones on more than one
FIP. For an F3200 panel the zones must be all of the same type, i.e. all
alarm zones or all relay zones, etc.