F3200 Operator's Manual Document No: LT0119
Network Systems
Page 11-24 29 July 2002 Issue 2.04
11.10.6 NETWORK ZONE TESTS
11.10.6.1 Function
To initiate a test of a zone at a remote FIP. The zone tests can:
· Test the circuit inputs of the selected alarm zone;
· Send test signals to the Brigade;
· Operate test an ancillary control zone, relay or open collector output.
· Auto reset test an alarm zone,
as if the test was initiated by an operator at the remote FIP. Tests at the remote FIP can
also be aborted.
If the network zone to be tested is on the local FIP, the test menus continue as if a local
zone number had been entered. Refer to Section 7.1 for details on local testing of alarm
zones, and Sections 8.5, 8.9 and 8.10 for testing of relays and open collectors.
11.10.6.2 Testing a Single Zone
OPTION: To prevent mapped outputs from operating, "ISOLATE" the zone first.
Refer Section 11.10.4.
From the base display, press:
OR
Where nnnnn is the number of the network zone to be tested.
If nnnnn is a network zone, a list of options is displayed, querying for the type of test to
be performed: Press
1: for alarm test (alarm zones)
2: for fault test (alarm zones)
3: for operate test (ancillary control zones, relays or open collector zones)
4: for auto reset test (alarm zones)
5: to abort a test in progress (all zone types)
Then press ACK to initiate the command. The command will be sent to the FIP with the
selected zone on it.