Caution!
The DIP switch in the thermostat must be set before it is
registered.
2. Select a channel
Use buttons < or > to move the pointer (LED flashes red) to a
preferred channel.
3. Lock selected channel
Note
It is recommended to register all channels to the
thermostat at the same time.
Press the OK button to select the channel for registration. The LED
for the selected channel starts flashing green.
Select all channels to be registered to the thermostat and continue to
the next step.
4. Activate tamper alarm
Optional: To activate tamper alarm for the thermostat, set the Disable
timer switch to Comfort mode ( ) before registering the thermostat.
5. Register thermostat
Gently press and hold the registration button on the thermostat,
release when the LED starts flashing green (located in the hole
above the registration button).
The selected channel LED in the room controller turns fixed green
and the registration is complete.
6. Set Disable timer switch
Optional: If tamper alarm was activated during registration, set the
Disable timer switch to preferred mode.
7. Exit registration mode
Press and hold the OK button on the room controller until the green
LEDs turn off to end registration and return to run mode.
To unregister already registered thermostats, see Unregister room
controller channels, Page 62.
40
|
Uponor Smatrix Base PULSE
|
Installation and operation manual