Assembly instances implemented by vacon® 100 family vacon • 73
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
8
8.3.4 Direction bit in VACON® FBFixedControlWord
If the “RunRev” bit in an Output Assembly has the value 1, and the “RunFwd” bit in the assembly has
the value 0, then the “Direction” bit 1 in the VACON® FBFixedControlWord is set to 1. Otherwise the
bit is set to 0.
8.3.5 Fault Reset bit in VACON® FBFixedControlWord
The “Fault Reset” bit in an Output Assembly is mapped to the “Fault Reset” bit 2 in the VACON®
FBFixedControlWord. Both bits are rising-edge sensitive.
8.3.6 Request Fieldbus Control bit in VACON® FBFixedControlWord
The “NetCtrl” bit in an Output Assembly is not mapped to the “Request Fieldbus Control” bit 8 in the
VACON® FBFixedControlWord because this way you can place the drive to the IO or keypad control
while fieldbus is active.
8.3.7 Request Fieldbus Reference bit in VACON® FBFixedControlWord
The “NetRef” bit in an Output Assembly is not mapped to the “Request Fieldbus Reference” bit 9 in
the VACON® FBFixedControlWord.
8.4 Mapping of VACON® data onto Standard Input Assemblies
This section specifies how the VACON® data is mapped onto the data in the Standard Input
Assemblies.
8.4.1 FBFixedStatusWord
See Chapter 9 "APPENDIX 1 - VENDOR CONTROL AND STATUS WORD DESCRIPTIONS".
8.4.2 Ready Indication bit in VACON® FBFixedStatusWord
The “Ready Indication” bit 0 in the VACON®VACON® FBFixedStatusWord is mapped to the “Ready”
bit in an Input Assembly which supports this bit.
8.4.3 Run/Stop Indication bit in VACON® FBFixedStatusWord
The “Run/Stop Indication” bit 1 in the VACON® FBFixedStatusWord is mapped to the “Running1”
and “Running2” bits in an Input Assembly which supports these bits. The state of the Running1 and

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals