4
vacon • 14 Commissioning
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
A fixed IP address is specified manually and it does not change. When the mode is changed from
DHCP to Fixed the fixed addresses are taken into use:
IP: 192.168.0.10
Subnet mask: 255.255.0.0
Default gateway: 192.168.0.1
4.1.2 Fixed IP address, subnet mask and default gateway
IP is divided into 4 parts. (Part = Octet). Changing these values does not have any effect if the current
IP mode is "DHCP". The values will become active when the mode is changed to "fixed IP". When
these values are changed and the mode is "fixed IP", the changes are taken into use immediately.
Subnet Mask marks all the bits of an IP address for the identification of the network and the sub-
network.
Gateway address is the IP address of a network point that acts as an entrance to another network.
4.1.3 Active IP address, subnet mask and default gateway
These values cannot be changed. If IP mode is "fixed" then it will display same value as in Fixed IP
address (5.3.3). If mode is "DHCP", the value is 0.0.0.0 when DHCP is retrieving IP settings or
169.x.x.x if it could not retrieve an address. Otherwise it shows currently active IP address.
4.1.4 MAC Address
The MAC address of the control board. MAC address (Media Access Control) is a unique address giv-
en to each network host. It is not editable.
4.2 EtherNet/IP parameters
Table 4. Parameters Menu
# Name Default
Range /
Accepted
Values
ID Definition
1
Protocol In Use 0 0…1 2417
d
0 = protocol not in use.
2
Output Instance 21 "20" (1),
"21" (2),
"23" (3),
"25" (4),
"101" (5),
"111" (6),
"128" (7),
"131" (8)
2418
d
Ethernet/IP input assembly
instance. See Chapter 8.

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V

Related product manuals