vacon • 64 Assembly instances implemented by vacon® 100 family
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8.1.2 ODVA Input instances
8.1.2.1
Assembly Instance 70 – Basic Speed Control Input
Table 61. Drive Mode Selection in Process Control
Drive Mode Process reference mapping
0ProcessDataIn1
4ProcessDataIn2
Other Not valid
Table 62.
Instance Octet Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
23
(length 6)
0
Net-
proc
NetRef NetCtrl
Fault
Reset
Run
Rev
Run
Fwd
1Drive Mode
2 Speed Reference (Low Octet)
3 Speed Reference (High Octet)
4 Process Reference (Low Octet)
5Process Reference (High Octet)
Table 63.
Instance Octet Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
70
(length 4)
0
Runnin
g1
Faulted
1
2 Speed Actual (Low Octet)
3 Speed Actual (High Octet)