6
vacon • 21 EtherNet/IP
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6.4.3 Connection Manager Object Error codes
These are the extended status codes used when the general status code is 1.
29
h
Member not settable
A request to modify a non-modifiable member was
received.
46
d
/ 2E
h
Service Not Supported
for Specified Path
The object supports the service, but not for the designated
application path (e.g. attribute).
Table 9. Connection Manager Object Error codes
Extended Status Descriptions
256
d
/ 100
h
Connection in use or duplicate forward open
259
d
/ 103
h
Transport class and trigger combination not supported
262
d
/ 106
h
Ownership conflict
263
d
/ 107
h
Target connection not found
264
d
/ 108
h
Invalid network connection parameter
265
d
/ 109
h
Invalid connection size
272
d
/ 110
h
Target for connection not configured
273
d
/ 111
h
RPI not supported
274
d
/ 112
h
RPI value(s) not acceptable
275
d
/ 113
h
Out of connections
276
d
/ 114
h
Vendor id or product code mismatch
277
d
/ 115
h
Product type mismatch
278
d
/ 116
h
Revision mismatch
279
d
/ 117
h
Invalid produced or consumed application path
280
d
/ 118
h
Invalid or inconsistent configuration application path
281
d
/ 119
h
Non-listen only connection not opened
283
d
/ 11B
h
RPI is smaller than the production inhibit time
294
d
/ 126
h
Invalid configuration size
295
d
/ 127
h
Invalid originator to target size
296
d
/ 128
h
Invalid target to originator size
297
d
/ 129
h
Invalid configuration application path
298
d
/ 12A
h
Invalid consuming application path
299
d
/ 12B
h
Invalid producing application path
306
d
/ 132
h
Null forward open function not supported
517
d
/ 205
h
Parameter error in unconnected request service
Table 8. General CIP error codes
Code Status name Description

Table of Contents

Other manuals for Vacon 100 flow

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 100 flow and is the answer not in the manual?

Vacon 100 flow Specifications

General IconGeneral
Protection classIP20
Communication interfaceRS-485
Operating temperature-10°C to +50°C
Storage temperature-40°C to +70°C
Ambient temperature-10°C to +40°C
Control methodSensorless vector control
Communication protocolsCANopen
ApprovalsCE, UL
I/O2 analog inputs
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature
Frequency range0 Hz to 400 Hz
Humidity5% to 95%, non-condensing
Voltage range208-240 V