Table 52: The technical data of the Vacon
®
100 HVAC AC drive
Technical item or function Technical data
Control characteristics
Switching frequency (see
parameter P3.1.2.3)
200-500 V
MR4-MR6:
1.5-10 kHz
Default: 6 kHz (except for 0012 2, 0031 2,
0062 2, 0012 5, 0031 5 and 0061 5: 4 kHz)
MR7-MR9:
1.5-6 kHz
Default: MR7: 4 kHz, MR8: 3 kHz, MR9: 2 kHz
600 V
MR5-MR9:
1.5-6 kHz
Default: 2 kHz
For a product that is configured for a C4
installation on IT network the maximum
switching frequency is limited to default
2kHz.
Automatic switching frequency derating in case of
overload.
Frequency reference:
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point 8-320 Hz
Acceleration time 0.1-3000 s
Deceleration time 0.1-3000 s