Vacon 100 - Page 149

Vacon 100
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 52: The technical data of the Vacon
®
100 HVAC AC drive
Technical item or function Technical data
Ambient conditions
Ambient operating tem-
perature
I
L
current: -10°C (no frost)…+40 °C
Up to 50 °C with derating (1.5%/1°C)
Storage temperature -40 °C…+70 °C
Relative humidity 0-95% R
H
, non-condensing, non-corrosive
Air quality:
chemical vapours
mechanical particles
Tested according to IEC 60068-2-60 Test Ke: Flowing
mixed gas corrosion test, Method 1 (H
2
S [hydrogen
sulfide] and SO
2
[sulfur dioxide])
Designed according to:
IEC 60721-3-3, unit in operation, class 3C2
IEC 60721-3-3, unit in operation, class 3S2
Altitude
100% nominal rating (no derating) up to 1000 m
1% derating for each 100m above 1000 m
Maximum altitudes:
208-240 V: 4000 m (TN and IT systems)
380-500 V: 4000 m (TN and IT systems)
380-500 V: 2000 m (corner-grounded network)
525-600 V: 2000 m (TN and IT systems, no corner
grounding)
Voltage for relay outputs:
Up to 3000 m : Allowed up to 240 V
3000 m-4000 m: Allowed up to 120 V
Corner grounding is allowed for MR4-MR6 (main volt-
age 208-230 V) up to 2000 m (see chapter 5.7 Installa-
tion in a corner-grounded network)
Ambient conditions
Vibration:
EN 61800-5-1
EN 60068-2-6
5-150 Hz
Displacement amplitude 1 mm (peak) at 5-15.8 Hz
(MR4-MR9)
Maximum acceleration amplitude 1 G at 15.8-150 Hz
(MR4-MR9)
Shock:
EN 60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: maximum 15 G, 11 ms (in pack-
age)
Enclosure class
IP21/UL Type 1: standard in entire kW/HP range
IP54/UL Type 12: option
NOTE!
For IP54/Type 12, a control panel adapter is neces-
sary.
TECHNICAL DATA, VACON® 100 HVAC VACON · 149