11 Connect the stripped cables.
a)
Connect the phase conductors of the mains
cable and of the motor cable into the correct
terminals. If you use a brake resistor cable,
connect its conductors into the correct
terminals.
b)
Attach the grounding conductor of each cable
to a grounding terminal with a grounding
clamp for grounding conductor.
c)
Make sure that the external grounding
conductor is connected to the grounding bar.
See chapter 2.4 Grounding and earth fault
protection.
d)
See the correct tightening torques in Table 26.
A
B
A. Connection of the cables
B. Make a grounding connection
in MR8
A
A. Make a grounding connection
in MR9
POWER CABLING VACON · 85