15 Attach the cable entry plate, and then the cable
cover.
16 For MR9, attach the cover of the drive (unless you
want to make the control connections first).
17 Make sure that the grounding conductor is
connected to the motor and also to the terminals
that are identified with
.
a)
To obey the requirements of the standard EN
61800-5-1, obey the instructions in chapter 2.4
Grounding and earth fault protection.
b)
Connect the protective conductor to 1 of the
screw connectors with a cable shoe and an M8
screw.
POWER CABLING VACON · 87