X5 AC Drive User’s Manual Chapter 7: X5 Parameters
DPD00089A - 99 - © 2009 Vacon Incorporated All Rights Reserved
801 Program Number
Default: 0
Range: 0 to 9999
Level 2, Macro
This parameter (Special Program Number) provides a way of enabling hidden functions in the drive and storing
parameters to the customer set.
Data Value
Special Function Configured
0 Standard program
1 Reset all parameters to factory default values (display = SETP).
2 Store customer parameter values (display = STOC).
3 Load customer parameter values (display = SETC).
4 Swap active parameters with customer stored settings.
10 Reset Total Run Time, parameter 108.
20 Enable writing of today’s time and today’s date parameter.
21 Store today’s time and today’s date parameter to RTC chip.
22 Abort time writing process.
30 Re-calibrate analog inputs (NOTE: no signal should be attached when performing this).
40 Clear Keeper records.
50 Allow model-dependent parameters to be recalled by USB. (See “Recalling Drive Parameters” on
page 53.
Note that data value 50 must be used to recall the following parameters via USB:
503 V/Hz Knee Freq 514 Motor RS
509 Rated Mtr Volt 515 Power Factor
510 Rated Mtr FLA 517 Single Phase
511 Rated Mtr RPM
Note also that the following parameters will never be recalled via USB:
490 Appl Macro 900 SIO Protocol
794 Drive Name 901 SIO Baud Rate
799 USB Config Mode 902 Comm Drop #
810 Language 916 Infrared Baud
811 Access Code
80 Disable Daylight Savings Time.
81 Enable Daylight Savings Time.
802 Start Options
Default: LS Lockout
Range: n/a
Level 2
The Start Options parameter configures the Line Start Lockout functionality of the drive. All data values ending with “2”
allow you to press the Enter key to store the customer speed reference value on the keypad. You must press and hold
the Enter key for two seconds to save the speed command. The following data values may be assigned:
Data Value
Description
LS Lockout (Line Start Lockout). If maintained contact run operators are used, they must be opened and then
re-closed for the drive to start after AC power is applied.
AutoStart When AC power is applied, if a Run command is present through the terminal strip, the drive will
start.
LSL w/FLY This setting has both LS Lockout and Catch on the Fly enabled at the same time.
Auto w/FLY This setting has both Auto-Start and Catch on the Fly enabled at the same time.
LS Lockout2 (Line Start Lockout). If maintained contact run operators are used, they must be opened and then
re-closed for the drive to start after AC power is applied.
AutoStart2 When AC power is applied, if a Run command is present through the terminal strip, the drive will
start.
LSL w/FLY 2 This setting has both LS Lockout and Catch on the Fly enabled at the same time.
Auto w/FLY2 This setting has both Auto-Start and Catch on the Fly enabled at the same time.
Table 7-2: Description of X5 Parameters (Page 29 of 40)