8 In-Tank Leak Tests Leak Test Frequency
8-2
NOTE: The screen examples shown in this procedure assume that you have selected the ALL TANK method. If you
choose SINGLE TANK, the tank number (for example “TANK 1”) replaces the phrase “ALL TANK” on each screen.
Leak Test Frequency
As mentioned, when you select a leak test method—ALL TANK in this example—the system displays the message:
NOTE: If you are entering setup information using the SINGLE TANK method and have already set up the test for
Tank 1, press TANK/SENSOR to choose the tank number you want to set up.
Do not press ENTER after changing the tank number. You must choose the Test Frequency, as described below,
before pressing ENTER.
You may choose from among the following leak test frequency options:
ON DATE
ANNUALLY
MONTHLY
WEEKLY
DAILY (QPLD will be selected if the Leak Test Frequency is set to daily, and the Leak Start Time is disabled.
This feature is only available if HRM has been enabled [see “TLS-350 Consoles” on page 4-1]).
AUTOMATIC (requires that the tank be assigned to a Line Leak Detector [see “Tank Selection” on page 10-7 for
PLLD, “Tank Selection” on page 11-6 for WPLLD, or “Pipe Label and Tank Identification” on page 12-1 for
VLLD], or a Pump Sense input - see Chapter 15)
CSLD (runs leak tests automatically during idle tank times and stores data for leak test reports)
NOTE: The CSLD option appears only when the tank is equipped with a 0.1 gph (0.38 lph) Mag probe, and
the
system has the CSLD software module key installed.
TEST ON DATE
To run the test on a specific date, press STEP in response to the ON DATE message. (To run the test using other
frequency options, follow the procedures described in the appropriate section below.) The system displays the
message:
Press CHANGE, and enter the date on which you want the tests to run. Enter the date in the format MM/DD/
YYYY. Press ENTER to confirm the date:
Press STEP to continue. The system displays the START TIME message. Follow the procedure under “Leak Test
Start Time” on page 8-7.
TEST ALL TANK:
ON DATE
TEST ON DATES: ALL TANKS
DATE: XX/XX/XXXX
DATE: XX/XX/XXXX
PRESS <STEP> TO CONTINUE