13-5
13 Volumetric Line Leak Tests Setting Up Additional Lines
You can set the test leak rate to 0.2 or 0.1 gph (0.76 or 0.38 lph). The default test rate is 0.2 gph. To accept the
default test rate, press STEP. To set the test rate to 0.1 gph, press CHANGE and press ENTER to confirm your
choice. The system displays the following message:
Setting Up Additional Lines
To set up line leak tests for additional lines, press STEP to return to the TEST SINGLE LINE message:
Press TANK/SENSOR to select the next line. Repeat the steps described above beginning with “Leak Test
Frequency” on page 13-2.
If you are setting up the test for All Lines, or have completed setting up all individual lines, the setup is complete.
Press FUNCTION to exit.
X.X GAL/HR
PRESS <STEP> TO CONTINUE
TEST SINGLE LINE: LINE 1
ON DATE