21-3
21 2-Wire C.L. Sensor Setup Setting Up Additional 2-Wire C.L. Sensors
If necessary, press CHANGE until you see the correct category. The category options are:
• ANNULAR SPACE •DISPENSER PAN
• MONITOR WELL •STP SUMP
• PIPING SUMP
When you display the correct category, press ENTER.
Setting Up Additional 2-Wire C.L. Sensors
If you have additional sensors to configure, press STEP until you see the ENTER SENSOR LOCATION message.
Press TANK/SENSOR to select another sensor and follow the procedures described above, beginning with“2-
Wire C.L. Sensor Location” on page 21-2.
If you have entered setup information for all sensors, press FUNCTION to exit.