Appendix B: Typical Setup Parameters - TLS-300 Leak Test Method Setup
B-3
The product code for all partners should be the same, e.g., tank 1 product code 1 manifold partner tank 4 product
code 1.
Leak Test Method Setup
Low Product:
Mag Type 8473
Mag Type 8493
00000
0000
Vol at 250 mm
Vol at 125 mm
Leak Alarm Limit 374 10 litres
Sudden Loss Limit 374 200 litres
Tank Tilt 0 10 mm
Manifold Tanks None Default*
Leak Min. Annual 0 60%
Periodic Test Type Standard Default
Annual Test fail Al. Disabled Default
Periodic Test Fail Al. Disabled Default
Gross Test Fail Disabled Default
Ann. Test Averaging OFF Default
Per. Test Averaging OFF Default
Tank Test Notify OFF ON
Tank Test Siphon B OFF Default
Delivery Delay 1 Minute 15 Minutes
Table B-4. Leak Test Method Setup
Parameter Default Set As
Test on Date Current T & D All Tanks Default
Start Time Disabled Default
Test Rate 0.76 LPH 0.38 LPH
Duration 2 Hours 4 Hours
Table B-3. In-tank Setup
Parameter Default Set As