Appendix B: Typical Setup Parameters - TLS-300 Comm Board (1, 2, etc.) Setup
B-2
Comm Board (1, 2, etc.) Setup
In-Tank Setup
Table B-2. Comm Board Setup
Parameter Default Set As
Baud Rate 1200 Comm Rate for
Third Party Equip.
Parity Odd Parity for Third
Party Equip.
Stop Bit 1 Stop Default
Data Length 7 Data Default
Table B-3. In-tank Setup
Parameter Default Set As
Product Label None As Tank Product
(e.g. UL UNLEADED)
Product Code 1 to 8 Default
Thermal Coeff. 000000 0.00126 Spirit, 0.00300 LPG
0.00081 DV
Tank Diameter 00000 As Tank Diameter
Tank Profile 1 Point 1 Point Flat Ends
4 Point Shallow-dished Ends.
20 Point Hemispherical Ends.
Linear for Vertical Cylindrical & Rectangular Tanks
Full Volume 00000 100% Tank Volume
Label Vol. As 100% Vol. As Tank Label
Float Size Depends on probe type Enter as used
Water Warning 00.00 25.0 mm
Water Limit 00.0 32.0 mm
Overfill Vol. 000% 99%
High Product 000% 98% if Label Volume >25,000 litres, or 96% if Label Vol-
ume <25,000 litres
Delivery Limit 001% Default