SmartCabinet2-E Series Computer Room Solution Product User Manual
Chapter 1 Product Overview 3
Cold and hot aisles are fully sealed
Air conditioner cooling capacity
Overall<75dB, ECO mode only
≤
50dB
1.5 Using Environment
1.5.1 Operating Environment
SmartCabinet 2-E products should be installed away from heat sources and sparks, avoid direct sunlight, and there
should be no corrosive gases and organic solvents in the room. The operating conditions are shown in Table 1-2.
Table 1-2 SmartCabinet2-E Operating Environment Requirements
The installation site needs to be level;
The height of using space should not be less than 2400mm (If the Airduct is include , The height of using
space should not be less than 2700mm);
In the computer room and office area, the front door is more than 1.2m away from the wall or obstacles
and the rear door is more than 1.0m away from the wall or obstacles.
< 2000m, air conditioners need to be derated for higher than 1000m
L+N+PE, 220Vac/230Vac/240Vac; 50/60Hz
Applicable form of
power grid
When the whole unit runs in high temperature and humidity environment, condensation water may appear
outside the front glass door and the display panel, which is a normal phenomenon and does not affect the
use.
1.5.2 Storage Environment
The storage environment of SmartCabinet 2-E products is shown in Table 1-3.
Table 1-3 Storage Environment for SmartCabinet 2-E Products
Indoor, clean (no dust, etc.)
1.5.3 Space
When installing SmartCabinet 2-E, enough space should be reserved to facilitate the installation and maintenance of
cabinets. The required space for opening the front and rear doors of the cabinet is shown in Figure 1-3.