EasyManua.ls Logo

Vertiv Tech SmartCabinet2-E Series - Air Conditioner System Maintenance

Default Icon
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartCabinet2-E Series Computer Room Solution Product User Manual
74 Chapter 4 Maintenance
Figure 4-1 Network Topology FIG SmartCabinet2-E
4.3.2 Air Conditioner System Maintenance
The air conditioner system maintenance mainly includes two aspects: electrical system inspection and cooling system
inspection.
Notices
When maintaining the device, the MCB should be disconnected and the power supply should be cut unless the power is required
for the commissioning project.
1. Electrical system inspection
The control panel and temperature sensor should be visually inspected every six months to determine if the
electrical connections are loose or not.
Check the maintenance one by one as follows:
1) Perform electrical insulation test of the whole unit, find unqualified contacts and handle them.
2) Tighten each electrical contact.
3) Clean dust off electrical and control components with a brush or dry compressed air.
Notices
All boards are forbidden to be plugged and unplugged with power on. The hot plug can generate a large amount of instantaneous
current, which may cause irreparable damage to the circuit. All maintenance for the control board must be performed after the
microprocessor controller is powered down.
2. Cooling system inspection
1) Fan
The running characteristics of the fan kit are continuous operation for 24 hours. Any abnormal airflow blocking factor
should be eliminated in time to avoid the damage of the cooling system and other system components.
2) Drainage pipe
In order to ensure the normal operation of the drain pipe, the water tray should be tested regularly. Make sure there
are no fine debris or leaks in the drainage pipe.
3) Cooling components
The cooling system components should be fully tested every month to discover abnormal operation phenomena in
time. The cooling line should be securely fastened and cannot vibrate with the frame of the wall, floor or equipment.
Check the cooling line for wear every six months.
4) Condenser
When the condenser air flow is obstructed, use a compressed air or fin cleaning agent (weak alkaline) to clean the
condenser and remove dust and debris that obstruct the air flow. When cleaning the fins with compressed air, the
direction of purging should be the direction of reverse air flow. Inspect the fins for rewinding or damage and perform
SmartCabinet2-P

Table of Contents