EasyManua.ls Logo

Vertiv Tech SmartCabinet2-E Series - UPS Power Distribution System Maintenance; Alarm Reference

Default Icon
87 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SmartCabinet2-E Series Computer Room Solution Product User Manual
76 Chapter 4 Maintenance
Check and tighten the circuit connector
Circuit board
Check circuit connection connector
Check the surface of the board for corrosion
Remark:
Signature:
Please copy this table for recording.
4.3.3 UPS power distribution system maintenance
1. Fan maintenance
Under continuous operation, the expected running time of the UPS fan is 20,000 hours to 40000 hours. The higher
the ambient temperature is, the shorter the fan life becomes.
During UPS operation, all fans should be checked periodically every six months to confirm that there is wind blowing
out from the vents on the rear panel of the UPS.
2. Check UPS status
Clean the UPS regularly, especially the vents, to ensure that airflow is freely circulated inside the enclosure and, if
necessary, cleaned with a vacuum cleaner. Confirm that there are no objects obstructing UPS ventilation. It is
recommended to check the running status of the UPS every six months.
The inspection contents include:
1) Check the UPS for faults. Check if the fault indicator is on, and if there is a fault alarm.
2) Check if the UPS is working on the bypass. Under normal circumstances, the UPS should operate in normal mode;
if the UPS is operating in bypass mode, the cause should be confirmed, such as: human action, overload, internal
fault, etc.
3) Check if the battery is in a discharged state. Under normal conditions, the battery should not be discharged. If the
UPS is running in battery mode, you need to confirm the cause, such as: power failure, battery test, human action,
etc.
4.4 Alarm reference
Table 4-4 Normal alarm reference
Alarm contents
Possible cause
Handling method
Environmental values
high temperature alarm
High temperature alarm value setting
is unreasonable
Check the high temperature alarm value of the temperature sensor
of the front door.
Overloaded
Check if the actual maximum thermal load exceeds the rated value
The fan is not operating normally
Check if the fan MCB is closed
Fan failure
Call the Vertiv Technical Service Hotline: 4008876510
Air conditioner cooling output failure
Call the Vertiv Technical Service Hotline
Cabinet door is not reliably closed
Check cabinet door and close it
Door status sensor
alarm
Cabinet door is not reliably closed
Check cabinet sealed door and close it
Poor installation of magnetic sensor or
sensor damaged
Re-adjust the installation gap or call the Vertiv Technical Service
Hotline
Belt type water sensor
alarm
Water in the detection zone
Check the computer room for leaks
Air conditioner condensate leak
Check if the condensate pipe connection is reliable

Table of Contents