AMBIENT TEMP, °F(°C) SUBCOOLING, °F(°C)
0 (-17.8) 22 (12.0)
10 (-12.2) 22 (12.0)
20 (-6.7) 22 (12.0)
30 (-1.1) 22 (12.0)
40 (4.4) 22 (12.0)
50 (10.0) 21 (11.7)
60 (15.6) 19 (10.8)
70 (21.1) 17 (9.3)
80 (26.7) 13 (7.2)
90 (32.2) 9 (5.0)
95 (35.0) 7 (3.9)
100 (37.8) 5 (2.9)
105 (40.6) 3 (1.8)
110 (43.3) 1 (0.7)
125 (51.7) 0
DPN002411, Rev. 8
Table 6.11 Target subcooling