6.3.4 Leak Checking for Unit and Field-installed Fluid Piping
The fluid systems in the Liebert CRV are factory-checked for leaks and may be shipped with a nitrogen
holding charge. At installation, check all fluid circuits for leaks.
NOTE: We recommend isolating the unit with field-installed shutoff valves during leak checking of
field-installed piping. When the units are included in a leak test, use of fluid for pressure testing is
recommended. When pressurized gas is used for leak testing the unit, the maximum recommended
pressure is 30 psig (207kPa) and tightness of the unit should be verified by pressure decay over time,
(<2 psig/hour [13.8kPa/hour]) or sensing a tracer gas with suitable instrumentation. Dry seals in fluid
valves and pumps may not hold a high gas pressure.
LIEBERT CRV
OPTION
CONDENSATE PUMP AND
HUMIDIFIER
CONDENSATE PUMP AND NO
HUMIDIFIER
NO CONDENSATE PUMP AND NO
HUMIDIFIER
MODEL 600 MM 300 MM 600 MM 300 MM 600 MM 300 MM
Top Connections Available Not Available Available Available Not Available Available
Bottom Connections Available Not Available Available Available Available Available
MODEL VOLUME, GAL., (L)
CR019RW 1.0 (3.78)
CR020RW 1.50 (5.7)
CR035RW 1.51 (5.7)
Table 6.16 Volume of internal water circuits—600-mm(24-in.)
and300-mm(12-in.)
Vertiv | Liebert CRV Installer/User Guide | 59