Temperature Integration Time
Adjusts amount of cooling/heating based on the length of time the temperature has deviated from the setpoint. The
time selected is the amount of time it will take cooling capacity to reach 100%. For example, if three minutes is selected,
cooling capacity will increase to 100% in three minutes.
NOTE: Three to five minutes of integration time is adequate for most applications. See Considerations when Using PI
Temperature Control on page28 .
NOTE: Only used when Temperature Control Type is PI.
Temperature Proportional Band
Adjusts the activation point of cooling/heating components based on deviation from setpoint by placing half of the
selected value on each side of the temperature control setpoint. A smaller number causes faster reaction to
temperature changes.
NOTE: Setting this too low causes short cycling of compressors.
Temperature Setpoint
Temperature that the unit maintains via cooling/reheat.
Temperature Setpoint Act
Read-only display of adjusted temperature setpoint when one of the following is active:
• Temperature compensation.
• BMS backup temperature setpoint.