Vertiv | NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000) | Rev. BB
76
Table 3:
SM-DU Switch Settings (cont’d from previous page)
DIP Switch S3
Set via
Software
Contactor
Type
Safe Mode
Dry Contact
Description of Status
1
2
3
4
Off
NA
Shunt parameter is set through DIP switch.
On
Shunt parameter is set via software.
(Note
1)
NA
Off
NA
Bi-Stable Contactor
(Note 1)
On Mono-Stable Contactor
NA
Off
NA
LVD / reconnection is disabled upon
communication failure.
On
LVD / reconnection is enabled upon
communication failure.
(Note 1)
NA
On LVD2 is a Dry Contact
Off LVD2
(Note 1)
DIP Switch S3
Shunt 5 Setting
Reserved
Calibration
Mode
Description
of Status
5
6
7
8
Off Off
NA
Shunt 5 is Disabled
(Note 1)
Off On Shunt 5 is Used for Battery
On Off Shunt 5 is Used for Load
On On Set via Software
NA
Off Operation Mode
(Note 1)
On Calibration Mode
Note 1: Setting for this system.

Table of Contents

Other manuals for Vertiv NetSure 7100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 7100 Series and is the answer not in the manual?

Vertiv NetSure 7100 Series Specifications

General IconGeneral
BrandVertiv
ModelNetSure 7100 Series
CategoryPower Supply
LanguageEnglish

Related product manuals