Chapter 5: Detailed description of parameters
109
The acceleration / deceleration time refers to the frequency from zero to the value set by
parameter P0.24.
When P024 is set to 1, the deceleration time is associated with the set frequency, if the
frequency setting often changes, the motor acceleration is variable, pay attention to the
application.
Base frequency changed via
UP/DOWN while running
This parameter is only valid if the frequency source is set digitally.
Use the ▲, ▼ or signal buttons on UP and DOWN to select how the frequency correction
is set, the target frequency is based on the operating frequency, increasing or decreasing,
or the basic setting. Two sets of differences are used for inverters in the deceleration
process, namely, if the inverter is running and the frequency is not set at the same time,
the difference selection parameter is very large.
Command binding to
frequency source
Binding operation panel command to frequency
source
Frequency source by digital setting
Impulse setting (S3), option
Binding operation panel command to frequency
source (0-9, the same as units)
Binding operation panel command to frequency
source (0-9, the same as units)
It is used to link three running command sources with nine frequency sources, making it
easier to implement sync switching.