Chapter 1: Technical parameters
7
1.3 Selected performance parameters of the V800
Type of
converter
used
Input
voltage
50/60 Hz
Engine
power
(kW)
Power wire cross-section
(mm2) *recommended
Recommended
fuses IEC 60269 gG
(A)
V 800-2S0004
1 phase
230 V
0.4
1.5
10
V 800-2S0007
0.75
1.5
16
V 800-2S0015
1.5
2.5
25
V 800-2S0022
2.2
4.0
32
V 800-2S0030
3.0
4.0
40
V 800-4T0004
3 phases
400 V
0.4
1.5
6
V 800-4T0007
0.75
1.5
6
V800-4T0011
1.1
1.5
10
V 800-4T0015
1.5
1.5
10
V 800-4T0022
2.2
1.5
10
V 800-4T0030
3.0
2.5
16
V 800-4T0040
4.0
2.5
16
V 800-4T0055
5.5
2.5
20
V 800-4T0075
7.5
4
32
V 800-4T0110
11
4
32
V 800-4T0150
15
6
40
V 800-4T0185
150/0185
18.5
10
50
V 800-4T0220
22
10
50
V 800-4T0300
30
16
63
V 800-4T0370
37
25
100
V 800-4T0450
45
25
100
V 800-4T0550
55
35
125
V 800-4T0750
75
50
160
V 800-4T0900
90
70
225
V 800-4T1100
110
95
250
V 800-4T1320
132
120
315
V 800-4T1600
160
120
350
V 800-4T2000
200
185
500