EasyManua.ls Logo

VYBO Electric Vector V800 - Group P9: Faults and Protection

VYBO Electric Vector V800
221 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4: List of function parameters - shorted
75
P8.47
Inverter
temperature
0°C - 150°C
100°C
P8.48
Fan control
0: The fan works only during operation
1: The fan works continuously
0
P8.49
Frequency at wake-
up
Frequency during sleep (P8.51)
maximum frequency (P0.12)
0.00Hz
P8.50
Delay of wake-up
0.0s - 6500.0s
0.0s
P8.51
Frequency during
sleep
0.00 Hz - frequency at wake-up (P8.49)
0.00Hz
P8.52
Delay of sleep
0.0s - 6500.0s
0.0s
P8.53
Running time
reached
0.0 min - 6500.0 min
0.0 min
Group P9: Faults and protection
Function
code
Parameter name
Setting range
Default
setting
Attribute
P9.00
Selection of overload
protection
0: protection disabled
1: protection enabled
1
P9.01
Increasing motor
overload protection
0.20 - 10.00
1.00
P9.02
Motor overload
warning coefficient
50% - 100%
80%
P9.03
Increasing overload
of DC overvoltage
0 - 100 (when activate the dynamic
braking, set 0 )
10
P9.04
Overvoltage stall
protective voltage
120% - 150%
130%
P9.05
Over current
increasing
0 - 100
20
P9.06
Over current
protection
100% - 200%
150%

Table of Contents