Chapter 5: Detailed description of parameters
167
Frequency selection for continuing to run
Default
0
0
Actual running frequency
P9.54
1
Set frequency
Setting range
2
The upper frequency limit
3
The lower frequency limit
4
Backup frequency for error
P9.55
Backuped frequency at error
Default
100.0%
Setting range
60.0 % - 100.0 %
If a fault occurs during the running of the inverter and the manner of solving the fault is set
to "Continue to run", the inverter displays alarm code and continues to run at the
frequency set in P9.54. The value in P9.55 is the percentage of the maximum frequency.
P9.56
Reserved
P9.57
Reserved
P9.58
Reserved
P9.59
Selection of activity in case of a sudden power
outage
Default
0
Setting range
0
Invalid
1
Deceleration
2
Deceleration to stop
P9.60
The action will suspend the voltage monitoring
during a sudden power outage
Default
0.0 %
Setting range
0.0 % - 100.0 %
P9.61
Power monitoring time in case of a sudden
power outage
Default
0.50 s
Setting range
0.00 s - 100.00 s
P9.62
Voltage during power failure
Default
80.0 %
Setting range
60.0 % - 100.0 % (bus voltage)
In case of a sudden power failure or a sudden drop in voltage, the DC bus voltage is
reduced. This feature allows the inverter to compensate for decreasing the DC bus voltage
by energy of feedback reducing the output frequency to maintain the continuous
operation of the AC motor.
If P9.59 = 1 in case of a sudden power outage or a sudden drop in voltage, the inverter will
decelerate.
After recovering the normal bus voltage, the inverter accelerate to the set frequency. If
the bus voltage remains normal for a time exceeding the value set in P9.61, the bus
voltage is normal.