Setting of source the required value of
PID
IMPULSE setting (S3), option
PA.00 is used to select the PID setting channel. The PID setting is a relative value ranging
from 0.0% to 100.0%. PID feedback is also a relative value. The purpose of the PID control
is the same PID and PID feedback setting.
Setting of source the feedback of PID
IMPULSE setting (S3), option
This parameter serves to select the PID feedback signal channel.
PID feedback is a relative value ranging from 0.0% to 100.0%.
Direction of action the PID
0: Action forward
If the feedback value is less than the PID setting, the inverter output frequency rises. For
example, winding voltage control requires a PID action forward.
1: Action backward
If the feedback value is less than the PID, the output frequency of the inverter will be
reduced. For example, unwinding tension control requires a reverse PID action. Note that