Chapter 6 Error checking and elimination
197
Overvoltage at
constant speed
1: The input voltage is too
high.
2: An external force drives
the motor during
deceleration.
1: Adjust the voltage to normal
range.
2: Cancel the external force or
install the braking resistor.
The input voltage is not
within the allowable range.
Adjust the input voltage to the
allowable range.
1: Instantaneous power
failure occurs on the input
power supply.
2: The inverter's input
voltage is not within the
allowable range.
3: The bus voltage is
abnormal.
4: The rectifier bridge and
buffer resistor are defective.
5: The drive board is
defective
6: The main control board is
defective.
1: Reset the fault.
2: Adjust the voltage to normal
range.
3, 4, 5, 6: Find technical
support.
1: The load is too high or
another motor is connected
to the motor.
2: The inverter model has a
too low power class.
1: Reduce the load and check
the motor and mechanical
condition.
2: Select an inverter of higher
power class
1: P9.01 is set improperly.
2: The load is too high or
another motor is connected
to the motor.
3: The AC drive model is of
too small power class.
1: Set P9.01 correctly.
2: Reduce the load and check
the motor and the mechanical
condition.
3: Select an inverter of higher
power class.
Power output
phase loss
(reserved)
1: The cable connecting the
AC drive and the motor is
faulty.
2: The AC drive's three-phase
output is unbalanced when
the motor is running.
3: The drive board is faulty.
4: The module is faulty.
1: Eliminate external faults.
2: Check whether the motor
three-phase winding is normal.
3, 4: Find technical support