Chapter 4: List of function parameters - shorted
65
Function
code
Parameter name
Setting range
Default
setting
Attribute
P5.28
IMPULS minimum
input
0.00kHz - P5.30
0.00kHz
P5.29
Corresponding
minimum input
impulse setting
-100.0% - 100.0%
0.0%
P5.30
IMPULS maximum
input
P5.28 - 100.00kHz
50.00kHz
P5.31
Corresponding
maximum input
impulse setting
-100.0% - 100.0%
100.0%
P5.32
Filter time of
impulse curve
0.00s - 10.00s
0.10s
P5.33
Selection of FI
curve
Units: Selection of FIV curve
1: Curve 1 (2-point, see P5.13-P5.16)
2: Curve 2 (2-point, see P5.18-P5.21)
3: Curve 3 (2-point, see P5.23-P5.26)
4: Curve 4 (4-point, see C6.00 - C6.07)
5: Curve 5 (4-point, see C6.08 - C6.15)
Tens: Selection of FIC curve (1-5, the
same as FIV)
Hundreds: reserved
321
P5.34
Set the FI to less
than the minimum
input
Units: Set the FIV to less than the
minimum input
0: Minimum value
1: 0.0%
Tens: Set the FIC to less than the
minimum input (0-1, the same as FIV)
Hundreds: reserved
000
P5.35
FWD delay time
0.0s - 3600.0s
0.0s
P5.36
REV delay time
0.0s - 3600.0s
0.0s