Chapter 4: List of function parameters - shorted
79
Function
code
Parameter name
Setting range
Default
setting
Attribute
P9.47
Selection of failure
protection action 1
.... X: Motor overload (OL1)
0: Deceleration to stop
1: STOP by stop mode
2: Continues in run
... X .: Reserved
..X ..: Phase loss (LO)
.X ...: External device error (EF)
X ....: Communication error (CE)
00000
P9.48
Selection of failure
protection action 2
....X: Reserved
0: Deceleration to stop
....X.: EEPROM error (EEP)
0: Deceleration to stop
1: STOP by stop mode
..X..: Reserved
.X...: Reserved
X....: Total time was reached (END1)
00000
P9.49
Selection of failure
protection action 3
....X:
0: Deceleration to stop
1: STOP by stop mode
2: Continues in run
...X.:
0: Deceleration to stop
1: STOP by stop mode
2: Continues in run
..X..: The total time of power on was
reached (END2)
0: Deceleration to stop
1: STOP by stop mode
2: Continues in run
.X...: Zero load
0: Deceleration to stop
1: STOP by stop mode
2: Continues to operate at 7% of the
rated motor frequency and recovers the
set frequency if the load resumes
X....: Loss of PID feedback
0: Deceleration to stop
1: STOP by stop mode
2: Continues in run
00000