SPEEDGATE Installation and Maintenance Manual Revision 1 - MAY 2023
119
TROUBLESHOOTING
Parameters Not Set
Error Descripon Cause
F�090
Controller not
parameterized.
The basic parameters (P.205, P.100 to P.103) for the TST
FU3F controller have not yet been set.
Maintenance Counter Exceeded
Error Descripon Cause
F�080
Fault: Maintenance is
required.
Service counter has expired.
Safety Circuit Faults
Error Descripon Cause
F�201
Internal Safety Circuit test
failure.
‒ Service switch OFF when aempng to enter
programming (parameterizing) mode.
‒ Internal parameter or EEPROM checks defecve.
Pressing the STOP key provides addional
informaon about the cause.
‒ Failed watchdog relay or failed circuit board relay.
F�211
External Stop 1 tripped. External Stop circuit was interrupted starng at Input 1.
F�212
External Stop 2 tripped. External Stop circuit was interrupted starng at Input 2.
F�360
Short circuit detected on
edge input.
Short circuit detected on edges with normally closed
contact.
F�361
Number of edge trips for
closing has reached set
limit.
Parameterized, maximum number of safety edge trips
during a gate cycle was exceeded.
F�362
Redundancy error with
short circuit.
‒ One of the processing channels for short circuit
detecon does not react idencally with the
second channel.
‒ Controller board defecve.
F�363
Interrupon on edge input. ‒ Connecon cable defecve or not connected.
‒ Terminaon resistor incorrect or missing.
‒ Jumper J600 incorrectly set.