EasyManua.ls Logo

Wieland SP-SDIO - Safety Technology Reference Values

Default Icon
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
Wieland Electric GmbH | BA000966 | 07/2016 (Rev. C)
73
Safety technology reference values
938446475
samosPRO COMPACT (SP-COPx without I/O expansion)
888559243
Table 45: Safety technology reference values for samosPRO COMPACT (without I/O expansion)
Characteristic values
Configuration of safety outputs
Output groups:
Q1/Q2, Q3/Q4, IQ1/IQ2, IQ3/IQ4
Safety Integ-
rity Level
(IEC 61508)
1
Category
(EN ISO
13849-1)
Performance
level
(EN ISO
13849-1)
1
PFHd
2
Single-
channel
or two-
channel
input
Two-channel outputs (with or without
test pulses)
SIL3 4 PL e 1.3 · 10
–9
Single-
channel
output Q
n
for an out-
put group
Test pulses at all outputs
of an output group acti-
vated
SIL3 4 PL e 1.4 · 10
–9
Test pulses at one output
of the output group acti-
vated and test pulses at
the other output of the
output group deacti-
vated.
The value indicated refers
to the output with acti-
vated test pulses.
SIL3 3 PL e 1.4 · 10
–9
Output test pulses deac-
tivated
SIL2 3 PL d 9.8 · 10
–9
1
For detailed information regarding the safety configuration of your machine/system, please
contact the Wieland Electric branch in charge of your area.
2
Average probability of a hazard-causing failure per hour
12.2
12.2.1

Table of Contents