Manual 37365A GCP-30 Series Packages - Genset Control
© Woodward Page 115/179
Enable 'Idle mode' via terminal 70
Parameter 210
Idle Mode
by term.70 ON
only accessible via LeoPC1
Enable idle mode via terminal 70 ON/OFF
OFF .............. This terminal is used as an alarm input.
ON ................ This terminal is used as control input. The discrete output pro-
grammed with the relay manager function 133 ("idle mode active")
enables/disables in accordance with the logical status of terminal 70
according to the configured NO/NC logic. Generally this discrete
output from the GCP must be wired to the "idle input" of the speed
governor normally.
Energized Energizing the terminal 70 discrete input enables the
idle mode. The message "Idle Mode" is displayed in
all operational modes (except STOP mode) when a
start request is initiated and during the post-run time
so long as there are no other message with a higher
display priority (i.e. pre-glow). The generator under-
voltage and underfrequency protections are disabled
and the warning limit value for the oil pressure input
is suppressed while in the idle mode. These protec-
tions are enabled after terminal 70 is de-energized
and the monitored frequency is measured within 1 Hz
of the rated generator frequency or after 60 seconds,
which ever occurs first.
De-energized The idle mode is disabled and the protections are
enabled again (refer to the description above).