Manual 37365A GCP-30 Series Packages - Genset Control
Page 172/179 © Woodward
Access
Parameter Setting range Default value Customer setting
ANALOG INPUTS CONFIGURATION
Analog input 6 VDO
ON/OFF ON on off on off
L
Name and unit
freely configurable Analog 6
Analog input 6 VDO
0 to 5 bar
0 to 10 bar
0 to 5 bar 0-5 bar
0-10 bar
0-5 bar
0-10 bar
Limit warning value
0.0 to 10.0 bar 2.0 bar
Limit shutdown value
0.0 to 10.0 bar 1.0 bar
Delay limit 1/2
0 to 650 s 1 s
Monitoring for
High limit mon. [high]
low limit mon. [low]
low limit mon. high
low
high
low
Analog input 7 VDO
ON/OFF ON on off on off
L
Name and unit
freely configurable Analog 7
Limit warning value
40 to 120 °C 80 °C
Limit shutdown
40 to 120 °C 90 °C
Delay limit 1/2
0 to 650 s 1 s
Monitoring for
High limit mon. [high]
low limit mon. [low]
High limit
mon.
high
low
high
low
Ana.in 12345678 SV.del.
Y/N NNNNNYNN
Ana.in 12345678 control
Y/N NNNNNNNN
OUTPUT CONFIGURATION
Configure outputs
YES/NO NO Y N Y N
Analg.out.12O121 Parameter
0 to 22 1
Analg.out.12O121 0-00 mA
OFF
0 to 20 mA
4 to 20 mA
0 to 20 mA OFF
0-20mA
4-20 mA
OFF
0-20mA
4-20 mA
Analg.out.12O121 0%
0 to 9,990 0
Analg.out.12O121 100%
0 to 9,990 200
Analg.out.122123 Parameter
0 to 22 1
Analg.out.122123 0-00 mA
OFF
0 to 20 mA
4 to 20 mA
0 to 20 mA OFF
0-20mA
4-20 mA
OFF
0-20mA
4-20 mA
Analg.out.122123 0%
0 to 9,990 0
Analg.out.122123 100%
0 to 9,990 200
Assignm.relay 1
refer to page 128 for more info 1
Assignm.relay 2
refer to page 128 for more info 2
Assignm.relay 3
refer to page 128 for more info 3
Assignm.relay 4
refer to page 128 for more info 4
Assignm.relay 5
refer to page 128 for more info 5
Assignm.relay 6
refer to page 128 for more info 84
Assignm.relay 7
refer to page 128 for more info 85