Manual 37365A GCP-30 Series Packages - Genset Control
© Woodward Page 173/179
Access
Parameter Setting range Default value Customer setting
ENGINE CONFIGURATION
Configure engine
YES/NO NO Y N Y N
Aux.services prerun
0 to 999 s 0 s
Aux.services postrun
0 to 999 s 0 s
Start-stop-logic for
DIESEL
GAS
EXTERNAL [EXT]
DIESEL DIESEL
GAS
EXT
DIESEL
GAS
EXT
Min.speed for ignit.
0 to 999 rpm 100 rpm
Ignition delay
0 to 99 s 3 s
Preglow time
0 to 99 s 3 s
Gasvalve delay
0 to 99 s 5 s
Max. attempts to start
1 to 6 3
Starter time
2 to 99 s 10 s
Start pause time
1 to 99 s 8 s
L
f lower before start
ON/OFF OFF on off on off
L
time f lower bef.start
0 to 999 s 5 s
L
f lower before start
ON/OFF OFF on off on off
L
time f lower bef.start
0 to 999 s 5 s
Fuel relay logic
Open to stop [OPEN]
Close to stop [STOP]
Open to stop OPEN
STOP
OPEN
STOP
Cool down time
0 to 999 s 15 s
Delayed engine monitoring
1 to 99 s 8 s
Firing speed reached f>
5 to 70 Hz 15 Hz
Speed detected V L1-L2 > 00.0%
5.0 to 25.0 % 5.0 %
Pickup input
ON/OFF ON on off on off
L
Number of pickup teeth
30 to 280 160
L
Gen.rated speed
0 to 3,000 rpm 1,500 rpm
COUNTER CONFIGURATION
Configure counters
YES/NO NO Y N Y N
Service interval in
0 to 9,999 h 300 h
Set oper.hours counter
0 to 65,000 h 0 h
Set start counter
0 to 32,000 0
kWh counter set in
kWh
MWh
kWh kWh
MWH
kWh
MWH
kWh counter set
0 to 65,500 kWh/MWh 0 kWh
XPD, XPQ
Time
00:00 to 23:59 00:00
XPD, XPQ
Year,month
00 to 99,01 to 12 00.00
XPD, XPQ
Day/weekday
01 to 31/1 to 7 00.0
BPQ This parameter is only available in the BPQ Package
XPD This parameter is only available in the XPD Package
XPQ This parameter is only available in the XPQ Package
L This parameter may only be accessed via LeoPC1 depending on the unit
GCP-31 This parameter is only available in the GCP-31 Packages
GCP-32 This parameter is only available in the GCP-32 Packages